Technical Data
Packaging |
3,79 litre plastic bottle (1 gallon) - 4x1 per case |
||
Colour |
Milky white (wet), Transparent (dry) |
||
Sealant |
Vinylacetat-Polymer |
||
Dispersion |
Water |
||
Weight |
3,7 - 3,9 kg per gallon |
||
Solid content |
35% - max. 40% |
||
Viscosity |
> 1 centistoke at +20°C |
||
Coverage |
0,4 to 2 gal/hr. seal rate |
||
Flexibility |
remains flexible indefinitely |
||
Time to test |
Dry to the touch upon application. Can test within 10 min. of application. |
||
Service temperature |
approx. -29°C to +249°C |
||
Moisture resistance |
very good |
||
Mildew resistance |
Mold & mildew resistant |
||
VOC |
10,7 g/l (dry sealant) (<0,35%) |
||
Pressure |
SMACNA: up to 10 inches w.g. |
||
Seal class |
Meets SMACNA seal class A |
||
|
|
||
Application |
|||
Temperature |
>40°F |
||
Consumption |
Internal coverage at all joints, seams and penetrations, 0,4 to 2 gal/hr. seal rate |
||
Clean up |
(Liquid) Mild soap and hot water, (Dried) Citrus-based cleaner or buckeye workout |
||
|
|
||
Storage |
|||
Temperature |
-17,8°C to +43°C |
||
Shelf-life |
24 months (2 years) |
||
Flammability |
Non-flammable |
||
|
|
||
Tests |
|||
VOC Germany |
The product under investigation meets the requirements according to the „Approval principles for the health-related evaluation of indoor construction products“ ( DIBt Announcements 10/2010) in conjunction with the NIK values of the AgBB in the version of June 2012. |
||
VOC France |
The product has been classified in the VOC emission class A+. The recommendation for the classification is given on the basis of the French regulation for the labelling of construction products or wall coverings, floor coverings, paints and varnishes with regard to the emissions of volatile pollutants, as published on 25 March 2011 (décret DEVL1101903D) and 13 May 2011 (arrêté DEVL1104875A). |
||
VOC Belgium |
The product under investigation meets the requirements of the „Royal Decree establishing the limit values for emissions into the indoor environment of construction products for certain intended uses (May 2014)“. |
||
Hygiene Germany |
Meets the requirements of VDI 6022 for microbial innards; suitable for use in HVAC systems. |
||
CMR substances France |
The tested product meets the requirements of the French Directive DEVP0908633A of April 30, 2009 and DEVP0910046A of May 28, 2009. |
||
|
|
||
Property |
Test method |
Result |
|
Mold growth |
UL1381 |
No evidence of growth |
|
VOC |
CDPH 1.2 (2017) |
Passed (≤ 0.5 mg/m³) |
|
Accelerated aging |
ASTM E2342-10 |
Passed |
|
Leakage reduction |
ASTM E2342-10 |
Passed |
|
Erosion |
UL1381 |
Passed |
|
Burning |
UL1381 |
Passed |
|
Durability |
Ul1381 |
Passed |
|
|
|
|
|
Preparation |
|||
First, manually repair any leaks found during duct inspection >5/8” span, and remove accumulated dust/dirt build-up in ducts if >1/8”. |
|||
NOTE: Ducts can be cleaned after Aeroseal application. |
|||
|
|||
Precautions |
|||
Use only in well-ventilated areas. Installers should wear dust or fume respirator if inhalation exposure is possible. Fume respirator should have organic vapor-type breathing cartridge if full, prolonged exposure to aerosol is necessary. Keep out of reach of children. Refer to full SDS sheet for health hazard information. (www.aeroseal.com/sds) For use and application by trained Aeroseal professional installers only. |