Packaging

3,79 litre plastic bottle (1 gallon) - 4x1 per case

Colour

Milky white (wet), Transparent (dry)

Sealant

Vinylacetat-Polymer

Dispersion

Water

Weight

3,7 - 3,9 kg per gallon

Solid content

35% - max. 40%

Viscosity

> 1 centistoke at +20°C

Coverage

0,4 to 2 gal/hr. seal rate

Flexibility

remains flexible indefinitely

Time to test

Dry to the touch upon application. Can test within 10 min. of application.

Service temperature

approx. -29°C to +249°C

Moisture resistance

very good

Mildew resistance

Mold & mildew resistant

VOC

10,7 g/l (dry sealant) (<0,35%)

Pressure

SMACNA: up to 10 inches w.g.

Seal class

Meets SMACNA seal class A

 

 

Application

Temperature

>40°F

Consumption

Internal coverage at all joints, seams and penetrations, 0,4 to 2 gal/hr. seal rate

Clean up

(Liquid) Mild soap and hot water, (Dried) Citrus-based cleaner or buckeye workout

 

 

Storage

Temperature

-17,8°C to +43°C

Shelf-life

24 months (2 years)

Flammability

Non-flammable

 

 

Tests

VOC Germany

The product under investigation meets the requirements according to the „Approval principles for the health-related evaluation of indoor construction products“ ( DIBt Announcements 10/2010) in conjunction with the NIK values of the AgBB in the version of June 2012.

VOC France

The product has been classified in the VOC emission class A+. The recommendation for the classification is given on the basis of the French regulation for the labelling of construction products or wall coverings, floor coverings, paints and varnishes with regard to the emissions of volatile pollutants, as published on 25 March 2011 (décret DEVL1101903D) and 13 May 2011 (arrêté DEVL1104875A).

VOC Belgium

The product under investigation meets the requirements of the „Royal Decree establishing the limit values for emissions into the indoor environment of construction products for certain intended uses (May 2014)“.

Hygiene Germany

Meets the requirements of VDI 6022 for microbial innards; suitable for use in HVAC systems.

CMR substances France

The tested product meets the requirements of the French Directive DEVP0908633A of April 30, 2009 and DEVP0910046A of May 28, 2009.

 

 

Property

Test method

Result

Mold growth

UL1381

No evidence of growth

VOC

CDPH 1.2 (2017)

Passed (≤ 0.5 mg/m³)

Accelerated aging

ASTM E2342-10

Passed

Leakage reduction

ASTM E2342-10

Passed

Erosion

UL1381

Passed

Burning

UL1381

Passed

Durability

Ul1381

Passed

 

 

 

Preparation

First, manually repair any leaks found during duct inspection >5/8” span, and remove accumulated dust/dirt build-up in ducts if >1/8”.

NOTE: Ducts can be cleaned after Aeroseal application.

 

Precautions

Use only in well-ventilated areas. Installers should wear dust or fume respirator if inhalation exposure is possible. Fume respirator should have organic vapor-type breathing cartridge if full, prolonged exposure to aerosol is necessary. Keep out of reach of children. Refer to full SDS sheet for health hazard information. (www.aeroseal.com/sds) For use and application by trained Aeroseal professional installers only.