Virga Jesse Hospital

The hospital pharmacy supply duct system should comply with the cleanroom standards. Therefore airtightness class C (EN1507) was recommended. After the performed air tightness tests it appeared that even class A could not be achieved. A solution had to be found to avoid a new installation of the supply ducts.

PROJECT

Building: Virga Jesse Hospital
City: Hasselt / Belgium
Date: 2017
AEROSEAL Partner: Stokjes NV
Executing company: Stokjes NV
Preseal leakage: 296.9 l/s
Postseal leakage: 15.6 l/s l/s
Reduction of leakage: 94,75%

PROJECT COURSE

Air ducts made out of sheet metal, connected with flange system. Sealing performed with 3 injections point. Leakage has been reduced by 94,75% in total. Therefore leakage class C (EN 1507) has been achieved for the whole pharmacy supply duct system.